Recalls and Service Alerts

Furnaces - Air Conditioners - Heat Pumps

Condensate Blow off on ARUF, ARPT and AVPTC Air Handlers

Type: Service Alert
Equipment: Air Handler
Recall or Alert Date: 06-03-2014
Serial Number: SR-060
Brands Affected: AmanaGoodman

Description of Problem:

We have received some reports of condensate blow off on ARUF/PT and AVPTC Smart Frame™ air handlers when installed in the horizontal left position. The majority of the reports involve the “D” chassis air handlers.

Testing has determined that air leaks around the triangle endplates and coil top plate caused condensate blow off and to resolve this issue redesigned triangle endplates and insulation on the top plate of evaporator coil has been added in production beginning serial date code of 1405.

Affected Products:

ARPT36D14 ARPT48D14
ARPT42D14 ARPT60D14
ARUF48D14 ASPT48D14
ARUF60D14 ASPT60D14
ASPT42D14 ASUF59D14
AVPTC42D14 AVPTC48D14
ARPT36C14 AVPTC60D14
ARUF30C14
ARUF36C14 ARPT18B14
ARUF42C14 ARPT24B14
ASPT30C14
ASPT36C14 ARUF18B14
ASUF39C14
ASUF49C14 ARUF24B14
AVPTC30C14
AVPTC36C14 ARPT30B14
ASPT42C14 ARUF30B14
ASPT48C14 AVPTC24B14
AVPTC48C14 ASPT24B14
DV48PTCC14 ASUF29B14

Source:

Maytag